Skip to content

Script for calculation maximum power flow of flowgate by SO UPS, JSC standarts

Notifications You must be signed in to change notification settings

f4ilfish/max-power-flow

Repository files navigation

maxPowerFlow ⚡

Intro

It is Python script for calculating Maximum Power Flow (MPF) in flowgate of power system. MPF determine according with standart of Russian System Operator of the United Power System ("SO UPS", JSC)

Technical requirments

Calculating requirments

  • Power system model .rg2 file
  • Flowgate .json file
  • Trajectory .csv file
  • Faults .json file

Manual

  1. Make yours .rg2 file by RastrWin3 and put it in /samples folder
  2. Run "main" file
  3. Input path to .json and .csv files forming flowgate and trajectory
  4. Input value of active power fluctuation

Example of script running:

>> Select path to flowgate .json: C:\...\samples\flowgate.json
>> Select path to faults .json: C:\...\samples\faults.json
>> Select path to trajectory .csv: C:\...\samples\vector.csv
>> Input positive power fluctuations: 30

Example of script output:

>> MPF in normal regime (0.8*Pmax): 2216.57
>> MPF by the acceptable voltage level in the pre-emergency regime (1,15*Ucr): 2757.89
>> MPF in the post-emergency regime after fault (0.92*Pmax): 2132.61
>> MPF by the acceptable voltage level in the post-emergency regime after fault (1.1*Ucr): 2339.69
>> MPF by acceptable current in normal regime (Iacc): 1787.14
>> MPF by acceptable current in the post-emergency regime after fault (Iem_acc): 1479.26


Explanation

About .rg2 files

To find out how to make a .rg file use RastrWin3 -> Помощь -> Справка -> User Manual EN

About flowgate .json

Use flowgate .json file such a this structure:

    {
	    "line_1": {
		    "ip": 17, 
		    "iq": 16, 
		    "np": 0
	    }, 
	    "line_2": {
		    "ip": 6, 
		    "iq": 11, 
		    "np": 0
	    }, 
	    "line_3": {
		    "ip": 4, 
		    "iq": 14, 
		    "np": 0
	    }
    }
Parameter Meaning Values
ip Node number according to the start of the line in .rg2 int
iq Node number according to the end of the line in .rg2 int
np Parallel line number in .rg2 usually 1 or 2

About faults .json

Use faults .json file such a this structure:

    {
	    "outage_of_6_11": {
		    "ip": 6, 
		    "iq": 11, 
		    "np": 0,
		    "sta": 1
	    }, 
	    "outage_of_4_14": {
		    "ip": 4, 
		    "iq": 14,
		    "np": 0,
		    "sta": 1
	    }
    }
Parameter Meaning Values
ip Node number according to the start of the line in .rg2 int
iq Node number according to the end of the line in .rg2 int
np Parallel line number in .rg2 usually 1 or 2
sta Line status 0 - on, 1 - off

About trajectory .csv

Use trajectory .csv file such a this structure:

    variable,node,value,tg
    pn,23,-3.0,1
    pn,24,-3.0,1
    ...
    pg,6,-4.0,0
    pg,7,-4.0,0
    pg,8,-2.0,0
    pg,9,-1.0,0
Parameter Meaning Values
variable Type of node in .rg2 pn - load, pg - generator
node Node number in .rg2 int
value Changing the power in the node float
tg Power factor in node float

About

Script for calculation maximum power flow of flowgate by SO UPS, JSC standarts

Topics

Resources

Stars

Watchers

Forks

Languages